1x12f MTP to 1x12f MTP 12-fiber trunk cable


  • MTP Trunks provides the backbone DataCenter cabling. Female version ot MTP connectors are used mainly for direct interconnection of MTP to LC modules or MTP to LC(SC) fanouts. Double jacket 12-fiber MTP trunk cables are used in the DataCenters application where additional protection of the cable jacket is needed. Outer diameter of cable 4.5mm is still quite small, on the other hand offers double protection of the fibers.
  • MTP® PRO connector optional

Temperature range
Indoor controlled environment (-10°C/+60°C)
Cable parameters
Jacket material
LSZH
Cable construction
Round double jacket cable – ruggedized

Outer diameter
3.0mm/4.5mm

Fiber count
12

Fiber type
SM OS2 or MMF OM3/OM4/OM5
Temperature range Operation: -10°C to +70°C
Storage: -25°C to +70°C
Installation: -5°C to +50°C
CPR
Cca-s1a, d1, a2
Connector parameters
MTP/MTP PRO SM MTP/MTP PRO MM
Compliance
US CONEC standard
US CONEC standard
Colour of housing
Green
Aqua/Magenta/Lime Green
Colour of boot
Black Black
Polish
Angled (APC) Flat (PC)
Insertion Loss
(acc. IEC 61300-3-4 method B)
<0,35dB
(@1310/1550nm)
<0,35dB
(@850/1300nm)
Return Loss
(acc. IEC 61300-3-6)
>50dB
(@1310/1550nm)
>20dB
(@850/1300nm)
Identification Traceability label with unique serial number on both ends of cable assembly.
Packaging
Each assembly in sealed PE bag, bulk pack in cardboard box. Longer lengths coiled on cardboard/wooden reel.